DW2 Air circuit breaker

Model: DW2-1600
Shell ass Rated Current Inm(A): 1600
Rated insulation voltage Ui(V): 1000
Rated impulse withstand voltage Uimp(kV): 12

Description

Product representative image
DW2image
Scope of Application
DW2-1600 universal circuit breaker has the characteristics of small size,high breaking capacity,multi-function and so on.
DW2-1600 is suitable for grid-connected operation and protection of general power distribution system,new energy power generation and distribution system,multi-power distribution network,inverter and distributed power rotary motor power supply.
DW2-1600 conforms to the circuit breaker class standard GB/T14048 .2 --Class B use category,AC-3 use category:
◎ Circuit breaker is suitable for AC 50Hz/60Hz rated working voltage 400V/690V
◎ Circuit breaker rated current 200A~1600A
◎ The circuit breaker has three and four poles
◎ With drawer type and fixed type
◎ Refundable wire connection with isolation function,symbol is "image.pngDW2 Air circuit breaker manufacture"
◎ Circuit breakers meet the following standards:
IEC60947-1 and GB/T14048 .1-2012 Low voltage switchgear and control equipment General
IEC60947-2 and GB/T14048 .2-2020 Low voltage switchgear and control equipment circuit breakers
IEC60947-4-1 and GB/T14048 .4 Low voltage switchgear and control equipment Electromechanical contactors and motor starters (including motor protectors)

Application Scenarios
The DW2 Series Air Circuit Breaker is designed for low-voltage power distribution systems requiring high breaking capacity, reliable protection and safe circuit isolation. It is suitable for AC 50Hz/60Hz power networks with rated operating voltages up to 690V and rated currents from 200A to 1600A.
With its compact structure and comprehensive protection functions, the DW2 series is widely used as an incoming breaker, bus coupler breaker or feeder breaker in various power distribution applications. It provides reliable protection against overload, short circuit and other electrical faults while ensuring continuous and stable power supply.

Industrial Power Distribution
Widely used in factories, manufacturing plants, mining operations and industrial automation systems for power distribution and equipment protection.
Renewable Energy Systems
Suitable for photovoltaic power stations, wind power systems, energy storage projects and inverter output distribution systems.
Commercial Buildings
Applied in shopping malls, office buildings, hotels, hospitals and public facilities where reliable low-voltage power distribution is required.
Utility and Infrastructure Projects
Installed in substations, distribution stations, water treatment facilities, transportation systems and municipal infrastructure projects.
Motor and Equipment Protection
Used in motor control centers (MCC), power distribution cabinets and large electrical equipment to provide switching, isolation and protection functions.

Normal working conditions
The ambient air temperature is -5 ℃~+40℃(beyond the range can be reduced);
The elevation of the installation site does not exceed 2000m;
The relative humidity of the air at the installation site does not exceed 50%at the maximum temperature of +40 °C,and can have a higher phase humidity at lower temperatures, such as 90% at 20 ° C. Special measures should be taken for occasional condensation due to temperature changes;
Pollution level is 3;
The installation category of the main circuit of the breaker is IV,and the installation category of the other auxiliary circuits and control circuits isⅢ;
The circuit breaker should be installed in a place where there is no danger of explosion, no conductive dust, no enough to corrode metal and destroy insulation;
The circuit breaker should be installed in a place where there is no rain or snow;
Operational conditions
The circuit breaker passes the test requirements of GB/T14048 .2,and the altitude is 2000m(more than 2000m capacity reduction);
Storage conditions:ambient air temperature is -5 ℃~+40℃.

Structural features
Compact and High-Performance Design
Features a compact structure with high breaking capacity, making it suitable for modern low-voltage distribution systems.
Comprehensive Protection Functions
Provides reliable overload, short-circuit and fault protection to ensure safe operation of electrical equipment and distribution networks.
Fixed and Draw-Out Versions Available
Available in both fixed-mounted and withdrawable configurations to meet different installation and maintenance requirements.
Reliable Isolation Function
Equipped with a visible isolation function for safer maintenance and operation of power distribution systems.
Multi-Pole Configuration
Available in 3-pole and 4-pole versions to suit different distribution applications.
Optimized Contact and Arc Extinguishing System
Designed to achieve fast fault interruption, improve electrical endurance and enhance operational reliability.
Easy Installation and Maintenance
Modular construction allows convenient installation, inspection and replacement of components.
Compliance with International Standards
Manufactured in accordance with IEC 60947-2 and GB/T 14048.2 standards for low-voltage circuit breakers.

Product Model and Its Meaning

DW2 Air circuit breaker
Technical Parameters
Model DW2-1600
Shell ass Rated Current Inm(A) 1600
Rated caurent In(A) 200、400、630、800、1000、1250、1600
Rated operating votage UelV) AC50Hz/60Hz     400、690
Rated insulation voltage Ui(V) 1000
Rated impulse withstand voltage Uimp(kV) 12
Power frequencywithstand voltage UM)1min 3500
Number of poles 3、4
N-Pole Rated curentIn(A) 100%In
Using categonies B
AC-3
Rated limit short-circuit breaking capacity AC400V 65
lcu(kA)(valid value) AC690V 50
Rated operating short-circuit breaking capacity AC400V 55
IcskA(vald value) AC690V 42
Rated Short-Circuit Making Capacity AC400V 143
lem(kA)(peak value) AC690V 105
Rated short-time withstand current (1S) AC400V 50
The lcw(kA)(valid value) AC690V 42
Totalinteruption time (without aditional delay)(ms) ≤30
Qosing time (ms) ≤70
EleciclLfe (cycles) AC400V In=200A~630A 1500
In=800A~1250A 1000
In=1600A 800
AC690V In=200A~630A 1000
In=800A~1250A 650
In=1600A 500
Mechaniclife(ydes) Maintenance-free 15000
Maintenance ongoing 20000
Externaldimensions Fxed type 3P 260×310×240
(W×H×Dmm 4P 330×310×240
Drawer type 3P 275×345×330
4P 345×345×330

External appearance and installation dimensions
DW2 Air circuit breakerDW2 Air circuit breaker

Related Products

ZYM1 Molded case circuit breaker
Breaker,Circuit,Protection,Installation

ZYM1 Molded case circuit breaker

RT Fuse
Fuse Links,Circuit Protection,Breaking Capacity

RT Fuse

HR17 Fuse switch disconnector
Switch,Fuse,Isolation,Protection

HR17 Fuse switch disconnector

LZZBJ9-10N、H
Current Transformer,Measurement,Distribution,Insulation

LZZBJ9-10N、H

Get a Free Quote

Our representative will contact you soon.
Email
Mobile/WhatsApp
Name
Company Name
Message
0/1000
inquiry

Get a Free Quote

Our representative will contact you soon.
Email
Mobile/WhatsApp
Name
Company Name
Message
0/1000